UL & FM APPROVALS
PROPERTY LOSS
PREVENTION
Product standards and approvals are ensuring quality, global
recognition, safety and standardization. Approvals and listings
are often required by the market and a listed mark shows
the customer that the product has been tested according to
some minimum requirements for its category. In addition, it
shows that the supplier has committed to regular tests and
audits as being performed by the approval organisation.
The UL and FM approvals are some of the most well
recognized global standards and being able to mark our
products with these adds great value.
AVK products with UL & FM approval
Since we always aim at the highest quality, most
of our products for fire protection applications
are approved according to both UL and FM. We
have thus committed to meet the standards and
requirements set by these well-recognized global
organisations and to continuously test and control
our product ranges accordingly.
Our UL listed and FM approved products count
dry and wet barrel hydrants, butterfly valves, NRS
gate valves, OS&Y gate valves, post indicators,
wall post indicators and swing check valves.
FM Approval
FM Global is a property insurance company
operating from the philosophy that most losses
can be prevented. They provide insurance
products and property loss prevention
engineering services to protect their clients’
worldwide operations.
FM Approval is part of the FM Global Group and
it is a testing and certification service. Products
that pass the five-step approval process are
issued the globally acknowledged FM mark to
support property loss prevention and to signify
that they will perform as expected.
8
UL standards
Underwriters Laboratories (UL) is a product
safety testing and certification company having
developed more than 1,600 standards. UL is
certifying, validating, testing, verifying, inspecting,
auditing, advising and educating customers in
100+ countries.
AVK wet barrel fire hydrants series 24
UL 246 standard for hydrants for fire
protection service:
These requirements cover the performance of
and methods for testing hydrants intended for
use in piping systems supplying water for fire
protection service.
In order to become UL Listed, a representative
sample of the product to be listed must be
tested and meet the safety requirements set.
Products having the UL mark are covered by the
Underwriters Laboratories follow-up program,
which continuously tests the products to ensure
that the UL standards and requirements are
always met.
The UL 246 approval tests include a 10-day
moist ammonia air stress cracking test, testing
of rubber parts according to UL 157 and tests of
operation, leakage and head loss.
FM class number 1511:
Shell strength is tested by a pressure of four
times the working pressure lasting for five
minutes, and after the test there should be no
evidence of damage. The standard also includes
testing seat leakage at two times working
pressure for five minutes without damage or
leakage to be seen.
Furthermore, hose outlet strength, stem strength
and head loss are tested.